- Generally on neutral grounding is provided at each voltage. There will be several voltage levels between the generation of the power and distribution of the power in the power system. Only one ground is provided for each voltage level of the power system
- Grounding of the power system is provided at the source and not at the load end
- Each of the major bus section in the system are grounded
- For generator grounding, neutral of the generator is grounding through a resistance which limits the stator fault current. The value of the resistor employed for the grounding the generator decides the percentage of the generator windings left unprotected
- Synchronous motors and synchronous capacitors are provided with reactance type of grounding. This reactance grounding provides additional reactance which provides additional lagging currents which nullifies the capacitive grounding currents
- When several generators are connected to a common neutral bus, the bus is connected to the ground through a single grounding device. Disconnect switches are used to ground the desired generators to the neutral bus
- When several generators are operating in parallel, only one generator neutral is earthed. This is to avoid the interference between the zero sequence currents
- In generating stations there is a provision to ground neutral of at least two generators, though one at a time. The other generator neutral is grounded when the first generator is out of service
- When there are one of the two supply sources, no switching equipment is used in the grounding circuit.
- For the protection purpose, the neutral point of the star side of the power transformer is usually grounded
- The star connected secondary sides of the protective CTs and PTs are grounded at one point. This ensures stable neutral, proper measurement of the voltages and currents, kWh and kVA on the secondary side measuring instruments and controls
- For the circuits between 3 kV and 33 kV resistance or reactance grounding is used. But for low voltages less than 600V and high voltages above 33 kV solid or effective grounding is used. Effective grounding limits the voltages of healthy phases to line-to-neutral values in the events of ground faults and also eliminates the arcing grounds. The effective grounding causes the ground fault currents of very high magnitudes flow through the machine. But modern day protection systems are very sensitive and fast operating so that faults are cleared in very short time
Setting goals gives you something to work towards in life and brings you a sense of purpose. When you set your goals, you are taking the first step toward achieving them. Writing down your goals is essential because it helps you switch from being in a passive state to being actively involved in your life.
Popular Posts
-
Factory Acceptance Test (FAT) procedure Visual Inspection Test Visual inspection with customer will be carried out on the LV switchboa...
-
Transformers are required throughout modern interconnected power systems. The size of these transformers ranges from as low as a few kVA ...
-
Wave trap is a parallel tuned inductor - capacitor tank circuit made to be resonant at desired communication frequency . It reduces ...
-
Dear Engineers spend some time to read this article fully which helps to crack most of the MNC interviews. Ultimately the following points a...
-
How to calculate Knee point voltage for CT Knee Point Voltage, Vk = [(VA/Is^2) + Rct]*ALF*Is VA = CT Burden, Is = Second...
-
This is the significance of saturation level of a CT core mainly used for protection purposes. The sinusoidal voltage of rated frequency ap...
-
kVA is the unit for apparent power. Apparent power consists of active and reactive power. Active power is the share of the apparent p...
-
Why is vector group important? Because it determines the phase angle displacement between the primary (HV) and secondary (LV) wi...
-
What are the most important skills of an electrical test engineer to have? This question can help the interviewer determine if you have the ...
Sunday, 28 April 2019
Neutral Grounding Practice in Power System
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment