CIRCUIT BREAKER TESTING

TEST
EQUIPMENTS USED
       1.    Insulation Resistance Measurement
       a.    5KV Insulation Tester (Make: Megger)
       b.    3 Pole timer <Egil> (Make: Megger)
       c.    Multimeter (Fluke)
       d.    CPC 100 (Make: Omicron)
       2.    Coil Resistance Measurement
       (Trip and Close)
       3.    Closing and Tripping coil pick up
       4.    Breaker Timer Test
       Close: <60ms
       Open: <50ms
       5.    Contact Resistance Measurement
       Per joint: <20µ ohm
       6.    Electrical & Mechanical Operational      check


*Electrical & Mechanical Operational Check Includes
·         Name Plate Details
·         Rack in/out check
·         Spring charge mechanism (Electrical & Mechanical)
·         Current drawn by spring charge motor & Spring charge time
·         Anti-pumping check, Open / Close indication check
·         Auxiliary contact checks & Counter Operation Checks
·         Tripping and Closing operation