As a protection CT may be required to deliver
high values of secondary current, the secondary winding resistance must be made
as low as practicable. Secondary leakage reactance also occurs, particularly in
wound primary current transformers, although its precise measurement is difficult.
The  non-linear  nature 
of  the  CT 
magnetic circuit  makes  it 
difficult  to  assess 
the definite ohmic value representing secondary leakage reactance. It
is, however, normally accepted that a current transformer is of the low
reactance type provided that the following conditions prevail:
a. The core is of the joint less ring type
(including spirally wound cores)
b. The secondary turns are substantially evenly
distributed along the whole length of the magnetic circuit
c. The 
primary  conductor(s)  passes 
through  the approximate  centre 
of  the  core 
aperture  or, if wound, is
approximately evenly distributed along the whole length of the magnetic circuit
d. Flux equalizing windings, where fitted to the
requirements of the design, consist of at least four parallel-connected  coils, evenly distributed along the whole
length of the magnetic circuit, each coil occupying one quadrant
Alternatively, when a current transformer does
not obviously comply with all of the above requirements, it may be proved to be
of low-reactance where: 
e. The composite error, as measured in the
accepted way, does not exceed by a factor of 1.3 that error obtained  directly 
from  the  V-I 
excitation characteristic of the secondary winding
 
 
 

 
No comments:
Post a Comment