Solidly Neutral Grounded Systems:
§ Solidly grounded systems are usually used in low
voltage applications at 600 volts or less.
§ In solidly grounded system, the neutral point is
connected to earth.
§ Solidly Neutral Grounding slightly reduces the
problem of transient over voltages found on the ungrounded system and provided
path for the ground fault current is in the range of 25 to 100% of the system three phase
fault current. However,
if the reactance of the generator or transformer is too great, the problem of
transient over voltages will not be solved.
§ While solidly grounded systems are an
improvement over ungrounded systems, and speed up the location of faults, they
lack the current limiting ability of resistance grounding and the extra
protection this provides.
§ To maintain systems health and safe, Transformer
neutral is grounded and grounding conductor must be extend from the source to
the furthest point of the system within the same raceway or conduit. Its
purpose is to maintain very low impedance to ground faults so that a relatively
high fault current will flow thus insuring that circuit breakers or fuses will
clear the fault quickly and therefore minimize damage. It also greatly reduces
the shock hazard to personnel
§ If the system is not solidly grounded, the
neutral point of the system would “float” with respect to ground as a function
of load subjecting the line-to-neutral loads to voltage unbalances and
instability.
§ The single-phase earth fault current in a
solidly earthed system may exceed the three phase fault current. The magnitude
of the current depends on the fault location and the fault resistance. One way
to reduce the earth fault current is to leave some of the transformer neutrals
unearthed.
§ Advantage:
1.
The main advantage of
solidly earthed systems is low over voltages, which makes the earthing design
common at high voltage levels (HV).
§ Disadvantage:
1.
This system involves all
the drawbacks and hazards of high earth fault current: maximum damage and
disturbances.
2.
There is no service
continuity on the faulty feeder.
3.
The danger for personnel
is high during the fault since the touch voltages created are high.
§ Applications:
1.
Distributed neutral conductor.
2.
3-phase + neutral
distribution.
3.
Use of the neutral
conductor as a protective conductor with systematic earthing at each
transmission pole.
4.
Used when the
short-circuit power of the source is low.
No comments:
Post a Comment