Resonant earthed system:
§ Adding inductive reactance from the system
neutral point to ground is an easy method of limiting the available ground
fault from something near the maximum 3 phase short circuit capacity (thousands
of amperes) to a relatively low value (200 to 800 amperes).
§ To limit the reactive part of the earth fault
current in a power system a neutral point reactor can be connected between the
transformer neutral and the station earthing system.
§ A system in which at least one of the neutrals
is connected to earth through an
1.
Inductive reactance.
2.
Petersen coil / Arc
Suppression Coil / Earth Fault Neutralizer.
§ The current generated by the reactance during an
earth fault approximately compensates the capacitive component of the single
phase earth fault current, is called a resonant earthed system.
§ The system is hardly ever exactly tuned, i.e.
the reactive current does not exactly equal the capacitive earth fault current
of the system.
§ A system in which the inductive current is
slightly larger than the capacitive earth fault current is over compensated. A
system in which the induced earth fault current is slightly smaller than the
capacitive earth fault current is under compensated
§ However, experience indicated that this
inductive reactance to ground resonates with the system shunt capacitance to
ground under arcing ground fault conditions and creates very high transient
over voltages on the system.
§ To control the transient over voltages, the
design must permit at least 60% of the 3 phase short circuit current to flow
underground fault conditions.
§ Example. A 6000 amp grounding reactor for a
system having 10,000 amps 3 phase short circuit capacity available. Due to the
high magnitude of ground fault current required to control transient over
voltages, inductance grounding is rarely used within industry.
No comments:
Post a Comment