Low Resistance Grounded:
§ Low Resistance Grounding is used for large
electrical systems where there is a high investment in capital equipment or prolonged
loss of service of equipment has a significant economic impact and it is not
commonly used in low voltage systems because the limited ground fault current
is too low to reliably operate breaker trip units or fuses. This makes system
selectivity hard to achieve. Moreover, low resistance grounded systems are not
suitable for 4-wire loads and hence have not been used in commercial market
applications
§ A resistor is connected from the system neutral
point to ground and generally sized to permit only 200A to 1200 amps of
ground fault current to flow. Enough current must flow such that protective
devices can detect the faulted circuit and trip it off-line but not so much
current as to create major damage at the fault point.
§ Since the grounding impedance is in the form of
resistance, any transient over voltages are quickly damped out and the whole
transient overvoltage phenomena is no longer applicable. Although theoretically
possible to be applied in low voltage systems (e.g. 480V),significant amount of
the system voltage dropped across the grounding resistor, there is not enough
voltage across the arc forcing current to flow, for the fault to be reliably
detected. For this reason, low resistance grounding is not used for low voltage
systems (under 1000 volts line to-line).
§ Advantages:
1.
Limits phase-to-ground
currents to 200-400A.
2.
Reduces arcing current
and, to some extent, limits arc-flash hazards associated with phase-to-ground
arcing current conditions only.
3.
May limit the mechanical
damage and thermal damage to shorted transformer and rotating machinery
windings.
§ Disadvantages:
1.
Does not prevent
operation of over current devices.
2.
Does not require a
ground fault detection system.
3.
May be utilized on
medium or high voltage systems.
4.
Conductor insulation and
surge arrestors must be rated based on the line to-line voltage.
Phase-to-neutral loads must be served through an isolation transformer.
§ Used: Up to 400 amps for 10 sec are commonly found on medium voltage
systems.
High Resistance Grounded:
§ High resistance grounding is almost identical to
low resistance groundingexcept that the ground fault current magnitude is
typically limited to 10 amperes or less. High resistance
grounding accomplishes two things.
§ The first is that the ground fault
current magnitude is sufficiently low enough such that no
appreciable damage is done at the fault point. This means that the faulted
circuit need not be tripped off-line when the fault first occurs. Means that
once a fault does occur, we do not know where the fault is located. In this
respect, it performs just like an ungrounded system.
§ The second point is it can control the
transient overvoltage phenomenon present on ungrounded systems if
engineered properly.
§ Under earth fault conditions, the resistance
must dominate over the system charging capacitance but not to the point of
permitting excessive current to flow and thereby excluding continuous operation
§ High Resistance Grounding (HRG) systems limit
the fault current when one phase of the system shorts or arcs to ground, but at
lower levels than low resistance systems.
§ In the event that a ground fault condition
exists, the HRG typically limits the current to 5-10A.
§ HRG’s are continuous current rated, so the
description of a particular unit does not include a time rating. Unlike NGR’s,
ground fault current flowing through a HRG is usually not of significant
magnitude to result in the operation of an over current device. Since the
ground fault current is not interrupted, a ground fault detection system must
be installed.
§ These systems include a bypass contactor tapped
across a portion of the resistor that pulses (periodically opens and closes).
When the contactor is open, ground fault current flows through the entire
resistor. When the contactor is closed a portion of the resistor is bypassed
resulting in slightly lower resistance and slightly higher ground fault
current.
§ To avoid transient over-voltages, an HRG
resistor must be sized so that the amount of ground fault currentthe unit will allow to flow exceeds the
electrical system’s charging current. As a rule of thumb, charging current is
estimated at 1A per 2000KVA of system capacity for low voltage systems and 2A
per 2000KVA of system capacity at 4.16kV.
§ These estimated charging currents increase if
surge suppressors are present. Each set of suppressors installed on a low
voltage system results in approximately 0.5A of additional charging current and
each set of suppressors installed on a 4.16kV system adds 1.5A of additional
charging current.
§ A system with 3000KVA of capacity at 480
volts would have an estimated charging current of 1.5A.Add one set of surge
suppressors and the total charging current increases by 0.5A to 2.0A. A
standard 5A resistor could be used on this system. Most resistor manufacturers
publish detailed estimation tables that can be used to more closely estimate an
electrical system’s charging current.
§ Advantages:
1.
Enables high impedance
fault detection in systems with weak capacitive connection to earth
2.
Some phase-to-earth
faults are self-cleared.
3.
The neutral point
resistance can be chosen to limit the possible over voltage transients to 2.5
times the fundamental frequency maximum voltage.
4.
Limits phase-to-ground
currents to 5-10A.
5.
Reduces arcing current
and essentially eliminates arc-flash hazards associated with phase-to-ground
arcing current conditions only.
6.
Will eliminate the
mechanical damage and may limit thermal damage to shorted transformer and
rotating machinery windings.
7.
Prevents operation of
over current devices until the fault can be located (when only one phase faults
to ground).
8.
May be utilized on low
voltage systems or medium voltage systems up to 5kV. IEEE Standard 141-1993
states that “high resistance grounding should be restricted to 5kV class or
lower systems with charging currents of about 5.5A or less and should not be
attempted on 15kV systems, unless proper grounding relaying is employed”.
9.
Conductor insulation and
surge arrestors must be rated based on the line to-line voltage.
Phase-to-neutral loads must be served through an isolation transformer.
§ Disadvantages:
1.
Generates extensive
earth fault currents when combined with strong or moderate capacitive
connection to earth Cost involved.
2.
Requires a ground fault
detection system to notify the facility engineer that a ground fault condition
has occurred.
No comments:
Post a Comment