The
 modern High Voltage SF6 circuit breakers have two parallel contact 
sets. The main contacts are low resistance contacts, which are silver 
plated, whereas arcing contacts are of tungsten-copper which helps in 
initiating arc quenching and current interruption. Measurement of the 
static contact resistance with the breaker in closed position gives the 
resistance of main contacts only because the arcing contacts are 
bypassed. Healthiness of main contacts only gets checked during this 
test. The minimum dc test current should be used according to 
manufactures specification; however, the IEC and ANSI recommended levels
 are: 50 A IEC 60694 and 100 A ANSI. 
Static contact 
resistance is measured by injecting a dc current through the breaker and
 measuring the milli-voltage drop. A four wire measurement method is 
used. The breaker must be in the closed position. If low resistance 
readings are obtained when testing the breaker contact resistance using a
 low current, then it is recommended to re-test the contacts at a higher
 current. A higher current will have the ability to overcome connection 
issues and oxidation on terminals, where a lower current may produce 
higher readings under these conditions
No comments:
Post a Comment